YOKOGAWA

YOKOGAWA Models ALR111, ALR121 Serial Communication Modules (for FIO)

The serial communication modules (ALR111 and ALR121) hardware specifications are as shown below.

Table  Serial Communication Module Hardware Specifications

Item Specifications

Model ALR111 ALR121

Interface RS-232C RS-422/RS-485

Connection method Point-to-point Point-to-point (RS-422)

Multipoint (RS-485)

Communication function Half-duplex

Synchronization method Start-stop synchronization

Transmission speed 1200/2400/4800/9600/19200/38400 bps (*1)

Transmission code ASCII/binary

Character length 7/8 bits

Stop bit length 1/2 bits

Parity check None/even/odd

Lag time after data transmission 1 ms (The lag time to start receiving data again after data transmission.)

Transmission distance Maximum 15 m Maximum 1200 m (total extended length)

Installation method Mounted on ANB10, ANB11, ANR10, AFF50, AFV10, AFV30, or AFV40

I/O wiring AKB131. AKB132. AKB133. AKB134 cables, etc. Cable with 3-pair shield, AKB161. or AKB162

Wiring connection D-sub-9-pin (female x 2) Clamped with terminal block’s M4 screws

(5 poles x 2)

Current consumption 0.5A

Weight 0.3 kg 0.3 kg

*1: The applicable transmission speed depends on the communication function, subsystems, and connection method.

An FCS collects data from subsystems or sets data with control calculations to subsystems using the builder functions

by way of serial communication modules.  A communication module selects only one communication function, thus

two ports must have identical communication functions.  It is not possible to select different communication function

for every port. The communication functions and those transmission speeds for each communication module are as

shown in the table below.

Table  Communication Functions for Communication Modules

Communication function ALR111 ALR121

FA-M3 communication DR DR

Modbus communication DR DR

MELSEC-A communication DR DR

YS communication with direct connection NIL SG

YS communication NIL SG

SLC500 communication SG SG

PLC-S communication SG SG

DR: Dual-redundant communication is applicable. SG: Only single communication is applicable. NIL: Not complied

Table  Transmission Speed by the Communication Function

Communication function Transmission speed (bps)

FA-M3 communication 1200/2400/4800/9600/19200/38400 (*1)

Modbus communication 1200/2400/4800/9600/19200

MELSEC-A communication 1200/2400/4800/9600/19200

YS communication (direct connection) 9600

YS communication 9600

SLC500 communication 1200/2400/4800/9600/19200

PLC-S communication 1200/2400/4800/9600/19200

*1: The transmission speed of 38400 bps is not available for some PC link modules

Hardware Requirements

The serial communication module runs on the following FCS.

AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D,

AFS30S, AFS30D, AFS40S, AFS40D,

AFG30S, AFG30D, AFG40S, AFG40D,

AFG81S, AFG81D, AFG82S, AFG82. AFG83S, AFG83D, AFG84S, AFG84D,

AFF50S, AFF50D

Software Requirements

The serial communication module runs on the control functions of the following FCS.

LFS1700 Control Function for Field Control Station (for AFV30/AFV40, Vnet/IP and FIO):

for AFV30/AFV40

LFS1500 Control Function for Field Control Station (for AFV10, Vnet/IP and FIO): for AFV10

LFS1300 Control Function for Standard Field Control Station (for V net and FIO): for AFS30/AFS40

LFS1330 Control Function for Enhanced Field Control Station (for V net and FIO):

for AFG30AFG40/AFG8

LFS1350 Control Function for Compact Field Control Station (for V net and FIO): for AFF50

Engineering Requirements

Works on LHS5100/LHMS5100 Standard Builder Function.

 INSTALLATION ENVIRONMENT

LFS1700 Control Function for Field Control Station (for AFV30/AFV40)

No. of ALR111/ALR121/ALE111/ALP111 or ALP121/ AGS813/AGP813

modules

No. of ALF111 modules

No. of all the communication modules

I/O data capacity for communication

No. of communication definition

No. of communication functions

Max. 8 units/FCS

(Max. 4 pairs for dual-redundant operation) (*1)

Max. 30 units/FCS

(Max. 15 pairs for dual-redundant operation)

Max. 30 modules/FCS (*1) (*2)

1000 words/ALR111. 1000 words/ALR121

128 definitions/ALR111. 128 definitions/ALR121

Communication I/O data capacity

ALP111 and ALP121 cannot be mounted on the same FCS together.

Max. 8 types/FCS (*1) (*3)

Max. 8000 words/FCS

(incl. data from other communication function)

This is the sum of ALR111. ALR121. ALE111. ALF111. ALP111 or ALP121. AGS813. and AGP813 modules.

This is the sum of communication functions of ALR111. ALR121. ALE111. and ALP111 or ALP121.

LFS1700 Control Function for Field Control Station (for AFV30/AFV40) + LFS1750 Node Expansion

Package (for 10 nodes)

No. of ALR111/ALR121/ALE111/ALP111 or ALP121/AGS813/AGP813

modules

No. of ALF111 modules

No. of all the communication modules

I/O data capacity for communication

No. of communication definition

No. of communication functions

Max. 16 units/FCS

(Max. 8 pairs for dual-redundant operation) (*1)

Max. 32 units/FCS

(Max. 16 pairs for dual-redundant operation)

Max. 48 modules/FCS (*1) (*2)

1000 words/ALR111. 1000 words/ALR121

128 definitions/ALR111. 128 definitions/ALR121

Communication I/O data capacity

ALP111 and ALP121 cannot be mounted on the same FCS together.

Max. 8 types/FCS (*1) (*3)

Max. 8000 words/FCS

(incl. data from other communication function)

This is the sum of ALR111. ALR121. ALE111. ALF111. ALP111 or ALP121. AGS813. and AGP813 modules.

This is the sum of communication functions of ALR111. ALR121. ALE111. and ALP111 or ALP121.