WOODWARD 5448-890 SPM-D10 Series One Breaker Synchronizer
SPM-D10 Series
One Breaker Synchronizer
APPLICATIONS
SPM-D10 Series
One Breaker Synchronizer
DESCRIPTION
The SPM-D10 is a microprocessor-based synchronizer
designed for use on three phase AC generators equipped
with Woodward or other compatible speed controls and
automatic voltage regulators. The SPM-D10 synchronizer
provides automatic frequency, phase and voltage matching
using either analog- or discrete output bias signals.
The HJV Package provides additional mains protection.
Part-No. 8440-1668 SPM-D1040B/XN is a direct
replacement of the SPM-A synchronizer.
DESCRIPTION
Synchronizing
• Phase match or slip frequency synchronization with
voltage matching
Protection ANSI
HJV Packages
• Three-phase sensing of mains voltage
• Mains over-/undervoltage
• Mains over-/underfrequency
• Mains phase/vector shift
Control outputs
Standard
• Discrete raise/lower for speed
• Discrete raise/lower for voltage
X & XN Packages
(59/27)
(81O/U)
(78)
• Analog bias outputs for voltage and speed
freely configurable for all levels (+/-1 V, +/
3 V, 0 to 5 V, 0.5 to 4.5 V, +/-10 V +/-5 V, 0
to 20 mA, +/-20 mA, and much more
configurable)
5448-890 SPM-D10
• Two-phase sensing of generator and bus
• Selectable operating modes like SPM-A (Run, Check,
Permissive, and OFF)
• Synchro-check possible
• Synchronization time monitoring
Isolated operation
• Frequency control
• Voltage control
Dead bus operation
• Closing of CB on demand
• Speed bias output configurable as 500 Hz
PWM output with adjustable voltage level
• Two raise/lower outputs configurable for either
speed or voltage
Operating Features
• Two-line Liquid Crystal display for operation
and alarm indication
• Synchroscope
• Indication of control activity and breaker state
• Multi-level password protection for parameters
• Configuration directly or via PC
• English or German language adjustable
FURTHER SPM-D SYNCHRONIZERS
• The SPM-D10/YB Series provides three-phase generator and bus measurement
refer to product specifications 37298 for more information
• The SPM-D11 Series provides load/var sharing
refer to product specifications 37292 for more information
• The SPM-D21 Series provides synchronizing for two circuit breakers and load control
refer to product specifications 37293 for more information
SPECIFICATIONS (for more see specific manuals)
5448-890 SPM-D10
Accuracy………………………………………………………………………………Class 1
Power supply……………………………………………[Standard] 24 Vdc (+/-25 %)
[N & XN Packages] 90 to 250 Vac/dc
Intrinsic consumption…………………………………………………………max. 10 W
Ambient temperature……………………………………………………….-20 to 70 °C
[N & XN Packages] -20 to 60 °C
Ambient humidity………………………………………………95 %, non-condensing
Voltage………………..Rated /Δ: [1] 66/115 Vac or [4] 230/400 Vac
Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac
Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac
Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV
Measuring frequency………………………………………………………..40 to 70 Hz
Linear measuring range up to……………………………………………….1.3×Vrated
Input resistance………………………………………….[1] 0.21 MΩ, [4] 0.696 MΩ
Max. power consumption per path…………………………………………< 0.15 W
Discrete inputs…………………………………………………………………… isolated
Input range…………………………………………………………..max. 250 Vac or dc
Input resistance……………………………………………………………approx. 68 kΩ
Relay outputs…………………………………………………………………….. isolated
Contact material…………………………………………………………………….AgCdO
Load (GP)…………………………………………………………….2.00 Aac@250 Vac
2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD)………………………………………………………………………………….
1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Housing………………………………………………Type APRANORM DIN 43 700
Dimensions……………………………………………………………..144×72×122 mm
Front cutout……………………………………………………138[+1.0]×67[+0.7] mm
Connection…………………………………………screw/plug terminals depending
on connector 1.5 mm² or 2.5 mm²
Front………………………………………………………………………insulating surface
Protection system…………………………………………..with correct installation
Front………………………………..