The 489-P5-LO-A20-E Low Voltage 4-20 mA Analog Output Relay

489-P5-LO-A20-E Technical Specifications

Part Number    489-P5-LO-A20-E

Manufacturer/OEM    GE Multilin / GE Grid Solutions

Series    489 Generator Management Relays

Input Voltage    20-60 VDC or 20-48 VAC

Included Draw Out Case    Draw Out Case Included if Listed On Quotation

Communication Ports Parity    None, Odd, Even

Harsh Environment Coating    Not Available on this Model

High-Set Phase Overcurrent Elements    Trip

IRIG-B Amplitude Modulated    2.5 to 6.0 Vpk-pk at 3:1 signal ratio

Low Forward Power Time Delay    0.2 to 120.0 s in steps of 0.1

Phase Overcurrent Voltage Restraint    Programmable Fixed Characteristic

Pollution Degree    II

Pulse Output Pulse Width    200 to 1000 ms in steps of 1

Tachometer Configurable    Assignable to Digital Inputs 4 to 7

Weight    10 lbs.

About the 489-P5-LO-A20-E

The 489-P5-LO-A20-E is a GE Multilin Relay belonging to GE’s SR family (which also includes the 469 Motor Protection Relay and 735 Feeder Protection Relay)

It is specifically designed for Generator Protection and can be used with both induction and synchronous generators

SR489-P5-LO-A20-E

The unit can operate at 25. 50. or 60 Hz

User Interface and Control

Features a 40-character display for viewing value messages, diagnostics, and setpoints

The front panel includes:

A numeric keypad

Status indicators

Value up and down keys

An RS232 port interface

Control and programming keys (reset, enter, menu, menu up, menu down)

This design allows for control without needing an external computer

Back Panel Connectivity and I/O

The back panel provides:

Twelve RTD inputs (field programmable)

Six output relays

Two RS485 communications ports supporting ModbusRTU or DNP 3.0 protocol (or both) up to 19200 bps

Four VT inputs

Four isolated 4-20 mA analog inputs and outputs

Seven assignable digital inputs

Seven CT inputs for three-phase output/three-phase neutral and ground current sensing

A separate safety and filter ground