KJ2201X1-BA1 SIS Logic Solver (SLS 1508)
Hazardous Atmosphere
II 3G Ex ec IIC Gc
FM16ATEX0056U
FM21UKEX0017U
CL. I Div. 2 GP. A,B,C,D
CL. I Zone 2 AEx/Ex ec IIC Gc
FM17US0286U
FM17CA0145U
Power Specifications
Local Bus Power
Field power
24 VDC at 1 A
4 A (maximum)
Environmental Specifications
Ambient
Temperature
Shock
Vibration
Airborne

KJ2201X1-BA1
Contaminants
Relative Humidity -40°C to +70°C
10g ½ Sinewave for 11msec
1mm Peak to Peak from 2 to 13.2Hz;
0.7g from 13.2 to 150Hz
ISA-S71.04 –1985 Airborne
Contaminants Class G3
5 to 95% Non-Condensing
Note: Refer to the product label for serial number
and location and date of manufacture.
Warning: This product has specific instructions for
installation, removal and operation in hazardous
areas. Refer to document 12P2046 “DeltaV™
Scalable Process System Zone 2 Installation
Instructions”. Other installation instructions are
available in the “DeltaV™ M-Series Hardware
Installation and Reference” manual.
Removal and Insertion
Field power supplied to this device, either at the field
terminal or as bussed field power through the
Carrier, must be removed before removing or
connecting the device.
This unit cannot be removed or inserted with system
power energized unless the area is known to be
non-hazardous.
Maintenance and Adjustment
This unit contains no user serviceable parts and
should not be disassembled
KJ2201X1-BA1